410. General requirements
Page 278: In Rule 4lOA3, third paragraph, change the bibliographic reference number as follows:
Neal. Hinghani. and l)oughty [I45j
Page 278: In Rule 410A3 EXCEPTION 4. change the text as follows:
Arc-rated equipment is not necessary for the employee’s head or face when the employee is wearing head protection meeting OSIIA 29 CFR 1910.135 [1148] if the estimated incident energy is less than 9 cal/cm’ for exposures involving single phase arcs in open air less than or 5 cal/cm2 for other exposures. Arc-rated equipment is necessary for the protection of the employee’s head and face and may consist of head protection meeting OSIIA 29 (‘FR 1910.135 and a face shield with a minimum arc ratin? of 8 cal/cm2 if the estimated incident-energy exposure is greater than 9 cal/cm2 and less than 13 cal/cm- for exposures involving single-phase arcs in open air or greater than 5 cal/cm’ and less than 9 cal/cm for other exposures. For exposures involving single phase arcs in open air, the arc rating for the employee’s head and face protection may be 4 cal’em’ less than the estimated incident energy.
Page 279: In Rule 4l0A3 EXCEPTION 5, change the text as follows:
For dc systems with voltages from 50 V to 250 V and 8000 A maximum fault current, in lieu of performing an arc hazard analysis. clothing with a minimum effective arc rating of 5 calcm’ shall be used.
Page 279: In Rule 410A3 NOTI I. change the bibliographic reference number as follows:Doan, “Arc Flash Calculations for Exposures to DC Systems” [B241
Page 279: In Rule 4l0A6 NOTE, change the bibliographic reference numbers as follows:OSIIA 29 (‘FR 1910.97, Subpart G [1147] OSHA 29 CFR 1910.268. Subpart R B49 FCC Bulletin No. 65 1B26]
Page 296: In Rule 441A1d NOTE 2, change the bibliographic reference number as follows:OSHA 29 CFR 1910.269 Appendix B [B50]
Page 296: In NOTE 3 of Rule 441A1d, add the bibliographic reference number after the citation of ANSI
C84.1-1995 as follows:NOTE 3: The voltage ranges are contained in ANSI C84.1-1995, Table 1 [B7].
Page 297: In Rule 441A4 NOTE 2, change the bibliographic reference number as follows:OSHA 29 CFR 1910.269 Appendix B [B50]
Page 301: In Table 441-1, change the bibliographic reference number in Footnote 7 as follows:OSHA 29 CFR 1910.269 Appendix B [B50].IEEE C2 pdf download.