IEC TS 63066-2017 pdf free.Low-voltage docking connectors for removable energy storage units.
This document applies to docking connectors (hereinafter referred to as accessories) incorporated in or fixed to electrical equipment, intended to connect removable energy storage units to a dedicated electric power conversion unit, to an energy consuming unit or to another energy storage unit.
These accessories are intended for DC and may include an earth1 contact and/or optional auxiliary contacts for signaling and data. These accessories have a rated current of up to 800 A and rated operating voltages not exceeding 1 000 V DC.
These accessories are not suitable for mating or unmating under load. These accessories are intended to be installed by instructed persons (IEC 60050-195:1998,195-04-02) or skilled persons (IEC 60050- 195:1998, 195-04-01) only.
The list of preferred ratings is not intended to exclude other ratings.
This document applies to accessories for use under environmental conditions as described in Clause 32.
These accessories are intended to be connected to current carrying parts in copper or copper alloy only, plated or not plated.
This document also applies to accessories intended to be used at extra-low voltage.
In locations where special conditions prevail, for example on board vehicles, additional requirements may apply.
These accessories are intended to be used with a specific charging system.
NOTE For conditions other than operation, additional requirements could be applicable, for instance IEC 62133 and the UN Recommendations on the Transport of Dangerous Goods section 38.338.3.
The tests are made on accessories fitted with the cables or conduits for which they are designed, screwed glands and fixing screws of bodies and covers being tightened with a torque equal to that of the tests of IEC 60309-1:1999, IEC 60309-1:1999/AMD1:2005 and IEC 60309-1:1999/A MD2:2012, 24.5 or 25.1, as appropriate.
Accessories are mounted as in normal use. Screwed caps or lids, if any, are tightened as in normal use. Accessories are mounted in a position as intended by the assembly. Tests are conducted with any doors, access panels, covers, etc., provided in the assembly both in the unmated, open, and closed positions. Accessories are placed in the most unfavourable position.
Accessories shall withstand fatigue acceleration.
Compliance is checked by inspection and by the lest of IEC 61373:2010, Clause 8, with three new samples. seventies for each direction according to Table 8. test variable TV7 and frequency range from IEC 61373:2011, Figure 2. All electric contacts are series connected and monitored during the test. There shall be no electric discontinuance of more than 1 ps.
Accessories shall withstand shocks.
Compliance is checked by inspection and by the test of IEC 6 1373:2010, Clause 10, with three new samples, Se verities for peak acceleration A and nominal duration D for each direction according to Table 8, test variable TV8. All electric contacts are series connected and monitored during the test, There shall be no electric discontinuance of more than I ps.IEC TS 63066 pdf download.